Dometic 630025 Instructions d'exploitation Page 68

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 134
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 67
68
C.C.
C.C.
C.
BIMETALBIMETAL
BIMETALBIMETAL
BIMETAL
This thermostat is designed to operate 12V DC single-
stage heat pump and an independent single-stage auxiliary
heat system. It is a manual changeover thermostat be-
tween heating, cooling and auxiliary heat. Operating tem-
peratures for both heating and cooling systems are change-
able to suit the comfort needs of the occupants.
This thermostat is used for a remote wall mounted
thermostat. The heat pump can have an air distribution box
or a ducted system. To check the operation refer to Section
1.3. Next, verify the wiring to the thermostat is correct.
Thermostat Wiring for Dometic Bimetal ThermostatThermostat Wiring for Dometic Bimetal Thermostat
Thermostat Wiring for Dometic Bimetal ThermostatThermostat Wiring for Dometic Bimetal Thermostat
Thermostat Wiring for Dometic Bimetal Thermostat:
Route the (10) conductor cable from the 14" x 14" opening
to the thermostat location. Leave enough cable within the
14" x 14" opening to connect to the low voltage cable. At the
thermostat location, leave about six (6") inches of cable
extending through the wall. Plug the thermostat cable into
the thermostat connector cable.
When an auxiliary furnace is used with the heat pump,
a two conductor cable must be routed from the furnace to
the thermostat location. Connect one wire from the furnace
to the violet wires with a wirenut. Connect the other wire
from the furnace to the green wire in the thermostat cable
and secure with a wire nut. Tuck the excess wire back into
the wall and fill opening with insulation to prevent drafts that
could affect the thermostat operation. Secure the thermo-
stat to the wall using the two screws.
NOTE: Verify the heat anticipator is set properly for the
auxiliary furnace. Failure to set the anticipator can cause
incorrect operation or failure of thermostat in AUX HEAT or
HEAT PUMP setting.
CABLE ASSEMBLY CONNECTORCABLE ASSEMBLY CONNECTOR
CABLE ASSEMBLY CONNECTORCABLE ASSEMBLY CONNECTOR
CABLE ASSEMBLY CONNECTOR
Before checking the thermostat for operation, first de-
termine that the thermostat is receiving DC power from the
relay board then disconnect the cable assembly from the
back of the thermostat.
Next, use a DC voltmeter and check from red wire or Pin
2 on cable assembly (positive [+] lead from voltmeter) to
brown wire or Pin 7 (negative [–] lead from voltmeter). You
should get a voltage reading of approximately 12V DC.
Next, move the negative (–) lead from the voltmeter to each
of the following wires or pins:
Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (PinBlue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin
Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (PinBlue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin
Blue (Pin 6), Yellow (Pin 5), Black (Pin 4) White (Pin
3)3)
3)3)
3). You should get a voltage reading of approximately 12V
DC on each wire. This indicates the relay board and cable
assembly are providing proper power and circuits to the
thermostat.
NOTENOTE
NOTENOTE
NOTE: Pin 2 (red wire) is positive DC volts when ambient
(outside) air is above 40°F. Pin 1 (violet wire) is positive DC
volts when ambient (outside) air is below 40°F.
If the above voltage checks are correct and the unit does
not operate correctly, check the thermostat.
If the above voltage checks are not as described, check
the relay board (Section 4.5) and the cable assembly (4.3).
To check the thermostat, first remove it from its mounting
on the wall. Then disconnect the thermostat assembly from
the cable assembly in the wall. Now you are ready to do a
continuity check on the thermostat assembly. Place the
positive (+) lead from the ohm meter on red wire (Pin 2) and
negative (–) lead from the ohm meter to the active pin or
wire to read continuity.
POLARITY IS IMPORTANT FORPOLARITY IS IMPORTANT FOR
POLARITY IS IMPORTANT FORPOLARITY IS IMPORTANT FOR
POLARITY IS IMPORTANT FOR
A PROPER CHECK TO BE DONEA PROPER CHECK TO BE DONE
A PROPER CHECK TO BE DONEA PROPER CHECK TO BE DONE
A PROPER CHECK TO BE DONE.
With System Switch in COOL, Fan Switch in HI AUTO
and room temperature ABOVE setpoint temperature, you
should have continuity between red wire (Pin 2) to black
wire (Pin 4), yellow wire (Pin 5) and blue wire (Pin 6). You
should NOT have continuity between red wire to violet or
white wires.
Vue de la page 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 133 134

Commentaires sur ces manuels

Pas de commentaire