11
Special Features
Auto Fan
When auto fan is selected the fan speed will vary depending on the
difference between the temperature set-point and the room tempera-
ture. In auto fan the compressor and fan cycle On and Off with the
thermostat.
When the difference is:
>5º ThefanoperatesonHIGH
<4º The fan operates on LOW
Compressor Time Delay
A time delay of approximately two minutes occurs any time the com-
pressor is required to begin the cooling or heat pump cycle.
Power Interruption
In the event the power to the air conditioner or control is interrupted,
the system will restart with the previous set points once power is
restored.
LCD Error Code
When the system determines that one of the faults listed below has occurred an error
code will be displayed in the LCD.
Error Code:
E1 Loss of communication between the Single Zone LCD thermostat and the mod-
ule board. LCD will cycle between E1 and the previous mode setting. System
will shut down.
E2 Open circuit or out of range Indoor Temperature Sensor. Heating and cooling
operation will be locked out. Fan operation can continue to operate.
E3 Shorted Indoor Temperature Sensor. Heating and cooling operation will be
locked out. Fan operation can continue to operate.
E4 Open circuit or out of range Outdoor Temperature Sensor (select models). Heat
Pump operation will be locked out. Air Conditioner, Fan and Furnace operation
can continue to operate.
E5 Open circuit or out of range Freeze Sensor. Air conditioner mode of operation
will be locked out. Furnace, heat strip, heat pump and fan mode of operation can
continue to operate but displays the last temperature set-point.